Group E1 Protection Parameters - Emotron VSB Series Instruction Manual

Table of Contents

Advertisement

Emotron VSB Instruction Manual
Param
Designation
E0-02 Selection when run time attained
E0-03 Consecutive run time setting
E0-04 Accumulative running time setting
E1-00 Overvoltage stall
E1-01 Overvoltage stall protection voltage
E1-02 Undervoltage stall
E1-03 Overload prealarm
E1-04 Overload prealarm threshold
E1-05 Overload prealarm detected time
E1-06 Protected action 1
2: Seven-segment mode
Hundreds place: over-modulation
adjustment
0: Disabled
1: Enabled
Unit's place: selection when
consecutive running time attained:
0: Continue to run
1: Stop and fault alarm
Decade: selection when
accumulative run time attained:
0: Continue to run
1: Stop and fault alarm
Hundreds place: unit of run time
0: Second
1: Hour
0.0s(h)~6000.0s(h)
0.0s(h)~6000.0s(h)

Group E1 Protection Parameters

0: Prohibited
1: Allowed
200V: 100%~120% default: 116%
400V: 120%~150% default: 135%
0: Disabled
1: Enabled
Unit's place: detection option:
0: Always detect
1: Detect at constant speed only
Decade: compared object:
0: Motor rated current
1: Drive rated current
Hundreds place: alarm option
0: Continue to run
1: Protection enabled and coast to
stop
20.0%~200.0%
0.1s~60.0s
Unit's place: reserved
Decade: temperature sampling
disconnection action:
0: Protection enabled and coast stop
1: Continue to run
- 60 -
Chapter 5 List of Parameters
Range
Factory
Attr
default
000
×
0.0
×
0.0
×
1
×
Model
×
Defined
0
×
000
×
180.0%
5.0s
0000
×