G ro u p d 0 P a ra m e te rs o f M o to r
When motor is selected as current load motor, please set motor parameters in Group d0.
d0-00

Type of motor

0: Ordinary motor
1: Variable frequency motor
The major difference between ordinary motor and variable frequency motor lies in the handling
of motor overload protection. Under low speed running, ordinary motor has poor heat
dissipation, so motor overload protection shall be derated at low speed. Since fan-based heat
dissipation of variable frequency motor is not affected by motor speed, low-speed overload
protection is not necessarily derated. Therefore, please set d0-00 to 0 when driving ordinary
asynchronous motor so as to protect the motor reliably.
d0-01

Power rating of motor

Motor rated voltage (220V)
d0-02
Motor rated voltage (380V)
d0-03
Rated current of motor
d0-04
Rated frequency of motor
d0-05
Number of poles of motor
d0-06
Rated speed of motor
Above-noted motor parameters must be correctly set according to motor nameplate. Please
select the motor that suits the power class of the drive, or the control performance of the drive
will drop dramatically.
Chapter 6 Specification of Parameters
Range: 0 - 1
Range: 0.4kW -
6553.5kW
Range: 0V~260V
Range: 0~480V
Range: 0.0A - 6553.5A
Range: 0.00Hz -
600.00Hz
Range: 1 - 80
Range: 0 - 65535 r/min
- 111 -
Factory default: 0
Factory default:
model defined
Factory default: 220V
Factory default: 380V
Factory default:
model defined
Factory default:
50.00Hz
Factory default: 4
Factory default:
model defined