2: seven-segment mode
This selection is valid only for V/f control. When five-segment mode is selected, the drive has
low temperature rise but relatively higher output current harmonic. Under seven-segment
mode, it has relatively higher temperature rise but lower output current harmonic. Under
vector control mode pattern, PWM is seven-segment mode.
Hundreds place: over-modulation adjustment
0: Disabled
1: Enabled
At low grid voltage or long-term heavy-duty operation, over-modulation can improve the
voltage utilization and enhance the maximum voltage output capacity of the drive. This
parameter takes effect only for V/f control, while over-modulation is enabled all the time
under vector control pattern.
Command when running
E0-02
time attained
Unit's place: command when consecutive running time attained
0: Continue to run
When consecutive running time of the drive attains the set value of E0-03, the drive will
continue to run.
1: Stop and fault alarm
When consecutive running time of the drive attains the set value of E0-03, the drive will display
fault code "to2" and coast to stop. Digital output terminal "consecutive running time attained"
will output ON. When E0-03 is set to 0, this parameter value is enabled.
Decade: command when accumulative running time reached
0: Continue to run
When accumulative running time of the drive attains the set value of E0-04, the drive will
continue to run.
1: Stop and fault alarm
When the accumulative running time of the drive attains the set value of E0-04, the drive will
display fault code "to3" and coast to stop. Digital output terminal "accumulative running time
attained" will output ON. When E0-04 is set to 0, this parameter value is enabled.
Hundreds place: unit of running time:
0: Second
1: Hour
Sets the unit of E0-03 consecutive running time and E0-04 accumulative running time.
Chapter 6 Specification of Parameters
Range: 000 - 111
- 125 -
Factory default:
000