CHECK 6
Fan Motor Signal Line
(1) Turn the power supply OFF.
(2) With the fan motor connector disconnected, measure the resistance between each pin, then make sure
that the resistance is more than the value mentioned in the following table.
1 White
2 Orange
3 Brown
GND
4 Blue
5
6
7 Red
CHECK 7
Electronic Expansion Valve Connector and Coil Resistance Criteria
(RZQ36/45LVA, RZQ45/48MYL)
(Orange)
(Yellow)
(Black)
(White)
(RZQ20/24LVA)
(White)
(Yellow)
(Orange)
(Black)
Service Diagnosis
1
2
(Red)
3
4
5
(Gray)
6
1
2
3
(Blue)
4
5
6
(Red)
Troubleshooting by Remote Controller
Measurement point
Judgement
1 - 4
1M or more
2 - 4
100k or more
3 - 4
100 or more
4 - 7
100k or more
Measurement point
Judgement
1 - 5
3 - 5
2 - 6
4 - 6
Measurement point
Judgement
1 - 6
2 - 6
3 - 6
4 - 6
40~50
40~50