SiME281501E
4.18 High Pressure Abnormality (Detected by the High
Pressure Switch)
E3
Error Code
Applicable
RZQ
Models
Method of Error
The protection device circuit checks continuity in the high pressure switch.
Detection
Error Decision
When the high pressure switch is actuated
Conditions
Defective high pressure switch
Supposed
Disconnection in high pressure switch harness
Causes
Defective connection of high pressure switch connector
Clogged indoor unit suction filter (in heating)
Dirty outdoor unit heat exchanger (in cooling)
Defective indoor unit fan motor (in heating)
Defective outdoor unit fan motor (in cooling)
Overcharge of refrigerant
Stop valve is not opened.
Defective outdoor unit PCB
High Pressure
The table below contains the preset high pressure switch values.
Switch Settings
RZQ20/24LVA
RZQ36/45LVA
RZQ45/48MYL
Service Diagnosis
High pressure switch
Model
Open
4.0 + 0/– 0.15 MPa
4.0 + 0/– 0.15 MPa
Troubleshooting by Remote Controller
Fuse
Close
6.3A/250V (F1U),
3.15A/250V (F6U)
3.0 ± 0.15 MPa
6.3A/250V (F1U, F3U, F4U),
5A/250V (F6U)
6.3A/250V (F1U (A1P), F2U,
3.0 ± 0.15 MPa
F3U, F4U)
5.0A/250V (F1U (A2P))
108