1 TROUBLESHOOTING FOR SERVO AMPLIFIER (DRIVE UNIT)
122
1.5 Remedies for warnings
Name: Simple cam function - Cam control warning
 The cam axis position restoration at a time of cam control start was a failure.
 The cam control is not normal.
Cause
Check method
(1)
After cam data was
Check if the power was
written, the cam control
cycled after the cam data
command was turned
was written.
on without cycling the
power.
(2)
After the cam control
Check if the cam control
command was turned
command was turned on
on, the servo-on was
during servo-on.
turned on.
(3)
The cam control
Check if the cam control
command was turned
command was turned on
on during servo motor
while the travel
driving, and the servo
completion was on.
motor stopped.
(4)
The cam control
Check if the home
command was turned
position return
on at the time of
completion is on.
incompletion of home
position return.
(5)
It became servo-off
Check if it is servo-off.
during cam control.
(6)
A home position is
Check if the home
erased during cam
position return
control.
completion is off.
(7)
It is stopped at a
Check if a software limit
software limit during
is reached.
cam control.
(8)
It is stopped at a stroke
Check if a stroke limit is
limit during cam control.
reached.
Check result
Action
The power was not
Cycle the power.
cycled.
The power was cycled.
Check (2).
The cam control
Turn on the cam control
command was not turned
command during servo-
on during servo-on.
on.
The cam control
Check (3).
command was turned on
during servo-on.
The cam control
Turn on the cam control
command was not turned
command while the
on while the travel
travel completion was on.
completion was on.
The cam control
Check (4).
command was turned on
while the travel
completion was on.
The home position return
Make a home position
completion is off.
return, and turn on the
cam control command.
The home position return
Check (5).
completion is on.
It is servo-off.
After servo-on, turn on
the cam control
command again.
It is servo-on.
Check (6).
The home position return
After the home position
completion is off.
return completion, turn
on the cam control
command again.
The home position return
Check (7).
completion is on.
A software limit is
After it is retracted from
reached.
the position of a software
limit, turn on the cam
control command again.
A software limit is not
Check (8).
reached.
A stroke limit is reached.
After it is retracted from
the position of a stroke
limit, turn on the cam
control command again.
Target
[A]
[GF]