Mitsubishi Electric Melservo-J4 Instruction Manual page 110

General-purpose ac servo. servo amplifier
Hide thumbs Also See for Melservo-J4:
Table of Contents

Advertisement

Alarm No.: 98
Alarm content
Detail
Detail name
No.
98.1
Forward
rotation-side
software stroke
limit reached
98.2
Reverse
rotation-side
software stroke
limit reached
Alarm No.: 99
Alarm content
Detail
Detail name
No.
99.1
Forward
rotation stroke
end off
99.2
Reverse
rotation stroke
end off
99.4
Upper stroke
limit off
99.5
Lower stroke
limit off
1 TROUBLESHOOTING FOR SERVO AMPLIFIER (DRIVE UNIT)
108
1.5 Remedies for warnings
Name: Software limit warning
 A software limit set with the parameter was reached for the positioning function.
Cause
Check method
(1)
A software limit was set
Check if the parameter
within the actual
settings ([Pr. PT15] to
operation range.
[Pr. PT18]) to the
operation range are
correct.
(2)
A point table of the
Check if the target
position data which
position of the point data
exceeds the software
to the operation range
limit was executed.
was correct.
(3)
A software limit was
Check if the JOG
reached by using the
operation or manual
JOG operation or
pulse generator
manual pulse generator
operation was executed
operation.
properly to the operation
range.
Check it with the check method for [AL. 98.1].
Name: Stroke limit warning
 The stroke limit signal is off.
Cause
Check method
(1)
The forward rotation
Check if the limit switch
stroke limit switch is
is connected correctly.
connected to LSP.
(2)
The forward rotation
Check if the forward
stroke end was
rotation stroke limit
exceeded during
switch turned off.
driving.
(1)
The reverse rotation
Check if the limit switch
stroke limit switch is
is connected correctly.
connected to LSN.
(2)
The reverse rotation
Check if the reverse
stroke end was
rotation stroke limit
exceeded during
switch turned off.
driving.
(1)
The upper stroke limit
Check if the limit switch
switch is not connected
is connected correctly.
to FLS of the controller.
(2)
The upper stroke limit
Check if the upper stroke
was exceeded during
limit switch turned off.
driving.
(1)
The lower stroke limit
Check if the limit switch
switch is not connected
is connected correctly.
to RLS of the controller.
(2)
The lower stroke limit
Check if the lower stroke
was exceeded during
limit switch turned off.
driving.
Check result
Action
The setting was out of
Set [Pr. PT15] to [Pr.
operation range.
PT18] correctly.
The setting was within
Check (2).
operation range.
The setting was out of
Set the point table
operation range.
correctly.
The setting was within
Check (3).
operation range.
It reached to the out of
Operate within the
operation range.
software limit.
Adjust properly the
parameters such as JOG
speed and multiplication
of the manual pulse as
necessary.
Check result
Action
It is not connected.
Connect it correctly.
It is connected.
Check (2).
It turned off.
Check operation pattern.
It is not connected.
Connect it correctly.
It is connected.
Check (2).
It turned off.
Check operation pattern.
It is not connected.
Connect it correctly.
It is connected.
Check (2).
It turned off.
Check operation pattern.
It is not connected.
Connect it correctly.
It is connected.
Check (2).
It turned off.
Check operation pattern.
Target
[A]
[GF]
Target
[A]
[GF]
[GF]