Erc112 Temperature Control; At Start Up; Defrost Mode - Delfield F18MC27-BSNP Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Operation

ERC112 Temperature Control

AT START UP

1. At initial start-up or anytime power is disconnected,
then reconnected to the unit, the control will go into

defrost mode.

2. The control will enter a DEFROST mode and the display
will read dEF. The compressor and condenser fan as
well as the evaporator fan will remain off until this
initial defrost is complete. This initial defrost cycle may
take up to 35 minutes to complete.
3. The display will continue to read dEF for an additional
30 minutes while the cooling cycle cools the box to the
set temperature.
4. Then the digital thermostat will display box
temperature.
5. The temperature control will cycle the compressor,
evaporator fan motor and condenser fan motor to
maintain box temperature at the control setting. For
more information see "Evaporator Fan Operation" on
page 9.
DEFROST MODE
The temperature control also monitors the evaporator
temperature and will turn off the compressor and
condenser fan motor when needed to allow accumulated
frost on the evaporator to clear. During this defrost cycle,
the digital temperature display will read dEF. After the
defrost cycle is complete, the temperature control will
return to a normal cooling cycle, but the display will
continue to read dEF until the evaporator returns to normal
cooling temperatures (up to 30 minutes).
The electronic temperature controller monitors evaporator
temperature and compressor run time to determine the
proper time for a positive defrost cycle. A defrost cycle
can occur as often as every 60 minutes under extremely
heavy usage. It can last a minimum of 2 minutes. When the
controller enters the defrost mode the compressor is shut
off and will remain off until the evaporator coil temperature
exceeds 41°F (5°C) or the controller reaches a time limit of
75 minutes.
10
Normal (°C)
Normal (°F)
Show set-point
V
Set to Defrost
Sensor 1 defect
Sensor 2 defect
High temperature alarm
Low temperature alarm
Line voltage too hight
Line voltage too low
Press upper or lower right button.
Display show actual set-point (blinking).
Increase set-point by pressing upper button. Max value
depends on parameters in control.
Decrease set-point by pressing lower button. Min value
depends on parameters in control.
Press upper left button for 5 seconds.
Start defrost.
Press lower left button for 5 seconds.
Unit goes into stand-by mode.
Press the lower left button again for 5 seconds.
Temperature Alarm
The alarm will flash HI or LO 90 minutes after the unit has
reached its alarm temperature point or after any power
interruption if the temperature is above or below the alarm
set points.
The high refrigerator temperature point is 50°F (10°C).
The low refrigerator temperature point is 25°F (-4°C).
Operation / Indication
Status
Displayed
Temp. [°C]
Temp. [°F]
Temp.
dEF / Temp
E01
E02
Hi
Lo
uHi
uLi
• If buttons untouched for 3 seconds returns to
normal.
• If buttons untouched for 3 seconds returns to
normal and stores new set-point.
• The display will read Off, then a period.
• The display will read On.
• The unit will then start up in the defrost mode,
and display will read dEF.
Part Number: 9291514 04/17
Section 3
Comments
Unit depends on setting
(parameters in control)
Depends on setting
(parameters in control
or as chosen by upper
left button)
Air sensor
Coil sensor
Automatically switching
at 2 sec rate