Advertisement

Operator control (software)
5.1 Browser-based web application
5.1.8.5

Data export

Data transfer is configured via the Modbus settings. All measured values are transferred
through this connection. As a bidirectional counter, the Data Manager measures active
power [W], reactive power [var], apparent power [VA] and power factor per phase and in
total, current [A] and voltage [V] per phase, and the network frequency [Hz].
The Data Manager provides a Modbus TCP server that uses the standard port 502 for
incoming connection enquiries. This port and the IP address must be configured to establish
a connection with the Data Manager.
Data export
In the case of data export, a CSV file is exported. This contains the instantaneous overall
consumption and the consumption of the individual sensors in € and kWh. To enable
recording of the values of the individual sensors in the CSV file, data transmission via
Modbus must be activated, and the individual phases must be assigned to the sensors. If
these settings are not made, only the overall consumption is recorded.
The following settings can be made in the "Data Export" dialog:
● Sensors that must appear in the CSV file
● Resolution: 15 min., 1 hour, 1 day and 1 week
● Time frame: If the period extends back more than one week, representation in increments
of 15 minutes is no longer possible.
40
7KT PAC1200 multichannel current measuring system
System Manual, 11/2016, 2514374103-02