Fig.6-6 Interface of control state
6.2.2 System parameter interface
Enter "system parameter". Main setting parameter items include "boot mode", "on/off-grid mode" and
"energy dispatching mode", as shown in Fig. 6-7.
Fig.6-7 System parameter interface
6.2.3AC parameter interface
Chapter VI Operation Control Display Panel 25
Enter "communication parameter" option. In this
interface, site of storage inverter, Baud rate and IP
address can be set. It is used for setting in case of
background and system station level monitoring and
communication, as shown in Fig.6-6.
Boot mode: please set it as "manual boot".
Off/on-grid mode": As for on-grid operation, close
AC breaker Q2 and set "on-grid mode"; as for
off-grid operation, disconnect AC breaker Q2 and set
"off-grid mode".
Energy dispatching mode: please set it as "AC
dispatching". If "DC dispatching" is set according
to the actual need, set "charging and discharging
current" and "charging and discharging power" in
DC parameter, as shown in 6.2.4.