GSM communicator G17F Safety requirements The security or fire alarm system should be installed and maintained by qualified personnel. Prior to installation, please read carefully this manual in order to avoid mistakes that can lead to malfunction or even damage to the equipment.
GSM communicator G17F Description Communicator G17F can upgrade any fire alarm panel for event signaling via cellular network. When input is violated, the communicator transmits an event message to Alarm Receiving Centre (ARC). Communicator can also inform customers about security system events in Protegus apps or with SMS messages.
6) Particular security control panel`s installation manual. Order them separately from your local distributor. Connect G17F to TrikdisConfig Communicator can be configured using TrikdisConfig software for MS Windows OS via USB cable or remotely. IMPORTANT: To use remote configuration function, Protegus service must be enabled (See chapter: Reporting window).
Status bar Name Description IMEI/Unique ID IMEI number of the communicator Status Action status Device Communicator type (shows G17F) Serial number Bootloader version Firmware version Hardware version State Connection status Admin Access level (shows up after access code is confirmed)
Serial – mandatory serial six-digit number (set previous step). Name – give name to the module. Firmware version – version will be shown when G17F is in working mode and detects module. Zones window → Zones settings tab Zones settings ...
GSM communicator G17F CID Code – zone Contact ID event code (will be set automatically when the zone function is selected). Zones window → Zones reporting tab Zones→Zones reporting This window will be shown only if at least one User is described in the 3.2 Users...
GSM communicator G17F Reporting window Primary and Backup channels Select communication Protocol – TCP/IP, UPD/IP, SMS, Protegus. If the TCP/IP or UDP/IP protocol will be used – enter ARC Domain or IP, Port and Encryption key. Choose the Backup protocol, and enter required data.
GSM communicator G17F ARC – selected event report will be sent to ARC. CID code – contact ID number. SMS event text – received SMS text after CID event is triggered. SMS restore text – received SMS text after CID event is restored.
GSM communicator G17F Physical installation process Insert SIM card into the holder Use only Nano SIM card. SIM card must be registered to the GSM network if GPRS communication will be used; enable mobile data service. To configure the communicator remotely, insert a SIM card with the PIN code request function disabled.
GSM communicator G17F Remote control SMS commands list SMS Commands are used to control the communicator remotely. As access code use “SMS password”, “_” represents a space. SMS command structure: Command_SMSpassword_Data. Examples For the exemplary purposes, SMS password is 123456.
Add communicator in Protegus Protegus service is a Web Service for remote intrusion or fire alarm self–monitoring and control of both Trikdis and 3rd party devices via Web, iOS, or Android apps. 1) Log in or sign in to www.protegus.eu.