Assembly Instructions

Assembly of a typical roof curb is shown in
1 . Set curbing parts A thru G per dimensions shown over
roof opening or on a level surface. Note location of
supply air opening. Check alignment of all mating screw
holes.
2 . Screw curbing parts together using fasteners provided.
Leave all screws loose until curb is checked to be square.
3 . Square entire curbing assembly and securely tighten all
screws.
Figure 2: Roof Curb Assembly (MPS 026G – 035F Example)
IM 1058-8 • MAVERICK II ROOFTOP SYSTEMS
Figure
2 .
4 . Position curb assembly over roof openings. Curb must
5 . Weld curb assembly in place. Caulk all seams watertight.
6 . Check that electrical connections are coordinated.
6
be level within 0.25 inches from side to side and 1.50
inches over its length. Check that top surface of curb is
flat with no bowing or sagging.
Remove backing from 0.25 × 1.50 wide gasket and apply
to surfaces shown by crosshatching.
m
I
eChanICal
nsTallaTIon
www.DaikinApplied.com