Daikin MPS015 F Installation And Maintenance Manual page 124

Maverick ii series heating and cooling r-410a refrigerant commercial packaged rooftop systems with energy recovery wheel and microtech iii unit controller
Table of Contents

Advertisement

Figure 98: Commission Unit – Keypad/Display Menu Structure
Commission Unit
Unit Set-Up
Timer Settings
SAF Set-Up
RF/EF Set-Up
Htg/Clg ChgOvr Set-Up
Cooling Set-Up
INV Cmp Set-Up
Econo Set-Up
Min OA Set-Up
Heating Set-Up
OA Fan Set-Up
Exp Valve Set-Up
Defrost Set-Up
Dehum Set-Up
Energy Rec Set-Up
D3 Set-Up
Alarm Configuration
Econo Set-Up
Min OA Set-Up
Clg Stage Time= 5min
Apply Changes= No
Chgover Temp= 65.0°F
Min OA Reset= None
Clg DB= 2.0°F
BSPOAOvrd= No
Econo Period= 30s
RstLmtSnsr= None
Econo Gain= 10
EXTERNAL RESET
Econo PAT= 60s
OA @ MinV/mA= 0%
Econo Max Chg= 10%
OA @ MaxV/mA= 100%
Econo Diff= 2.0°F
Min V/mA= 0.0V
Clg Reset= None
Max V/mA= 10.0V
Min Clg Spt= 55.0°F
CO2 RESET
Min Clg Spt @= 0
IAQ Reset= Yes
Max Clg Spt= 65.0°F
PPM@DCVLmt= 800PPM
Max Clg Spt@= 100
PPM@VntLmt= 1000PPM
IAQ PPM= XXXXPPM
Min PPM= 0 PPM
Max PPM= 2000 PPM
V/A @Min PPM= 0.0/V
V/A @Max PPM= 10.0/V
CFM RESET
OA Flow= XXXXXCFM
MinOAFlwSpt= 2000CFM
Field Stn Rst= Yes
Field Stn Cfg= VDC
Min CFM= 0 CFM
Max CFM= 10000 CFM
V/A @Min CFM= 0.0V
V/A @Max CFM= 10.0V
OA CFM DB= 3%
OA CFM Period= 30s
OA CFM Gain= 0.1
OA CFM Max Chg= 5%
IM 1058-8 • MAVERICK II ROOFTOP SYSTEMS
Unit Set-Up
Timer Settings
Space Sensor= Loc/Net
Service Time= 0min
Eng Units= English
Start Up= 180s
Unit Name= xxxxxxxxxxxx
Recirculate= 180s
Rapid Start= No
Zero OA Time= 0min
Rapid Start Tm= 10min
Tnt Override= 120min
DO10 Clg= FanOp
Post Heat= 0s
Pwd Timeout= 10min
Low DAT= 6min
ClgStateDelay= 300s
Clg Stg Time= 5min
Htg Stg Time= 5min
MinExStrtTm= 120s
MinExStopTm= 120s
ER Whl Stg Tm= 5min
ER Whl Off Tm= 20min
FAN SPEED RESET
Min Clg Spd= 40%
Des Clg Spd= 100%
BSP RESET
MinRFEFTm= 120s
BSP OvdST= 5s
BSP OvdGain= 0.2
BSP OvdMaxChg= 4%
DAMPER LIMITING
RstTLmt= 32.0ºF
RstTSmplTm= 5s
RstTGain= 0.2
RstPAT= 60s
RstTMaxChg= 4%
0–30% OA Max= 30%
Min Inc Rate= 0.03
Max Inc Rate= 1.0
a
– k
PPendIx
eyPad
SAF Set-Up
SAF Ctrl= DSP
AplyInputChgs= No
Min Clg Spd= 40%
CO2 Input= None
Max Clg Spd= 100%
CFM Input= None
Min Htg Spd= 40%
BSP Input= No
Max Htg Spd= 100%
SPEED CONTROL
Space Period= 30s
Rem SAF Cap= 25%
Space Gain= 1.5
DSP CONTROL
Space PAT= 100s
DSP DB= 0.1in
Space Max Chg= 10%
VFD Ramp Time= 60s
Min Period= 5s
Min PPM= 0PPM
Max Spd Chg= 15%
Max PPM= 2000PPM
V/A @ Min PPM= 0V
V/A @ Max PPM= 10V
Min SAF PPM= 800PPM
Max SAF PPM= 1100PPM
Min PPM Spd= 50%
Max PPM Spd= 100%
Heating Set-Up
OA Fan Set-Up
Htg Stage Time= 5min
OA FAN STATUS
Htg DB= 2.0°F
OA Fan1 Spd= XXX%
Htg Period= 60s
OA Fan1 Cmd= XXX%
Htg Gain= 0.8
OA Fan1Amps= XX.XA
Htg PAT= 120s
Fault Code Details
Htg Max Chg= 10%
OA Fan2 Spd= XXX%
Htg Lo OAT Lk= 0.0°F
OA Fan2 Cmd= XXX%
Htg Hi OAT Lk= 55.0°F
OA Fan2Amps= XX.XA
EffHtgHiOATLk= 55.0°F
Fault Code Details
SuplHtgHiOATLk= 55.0°F
REFRIG CIRCUIT STATUS
OAT Diff= 2.0°F
PTS= XXX.Xpsi
Htg Reset= None
PTD= XXX.Xpsi
Min Htg Spt= 55.0°F
Disch Sat Tmp= XXX.X°F
Min Htg Spt @= 0
EffDshSatTSpt= XXX.X°F
Max Htg Spt= 120.0°F
OA Temp= XXX°F
Max Htg Spt@= 100
INV Fin Temp= XXX°F
Min DAT Ctrl= Yes
OA FAN SET UP
Min DAT Limit= 55.0°F
DischSatTDiff= 15°F
Occ Heating= Yes
DischSatTDB= 2.0°F
Unocc Diff= 55.0°F
OA Fan Period= 10s
Htg Wmup Tm= 60s
OA Fan Gain= 0.5
Htg Hld Period= 240s
OA Fan PAT= 20s
MWUSensor= RAT
IFB COMM STATUS
124
/d
m
s
IsPlay
enU
TrUCTUre
1 ZONE VAV CONTROL
CFM CONTROL
Min CFM= 0CFM
Max CFM= 10000CFM
V/A @ Min CFM= 0V
V/A @ Max CFM= 10 V
SAF CFM DB= 3%
SAF CFM Period= 30s
SAF CFM Gain= 0.1
SAF CFM MxChg= 5%
CO2 CONTROL
BSP CONTROL
BSP DB= 0.01in
BSP Period= 5s
BSP Gain= 0.2
Max Spd Chg= 4%
SAF SETUP
SAF Ctrl Dly= 30s
Min Speed= 25%
VAVBox Out= _________
Max Vent Speed= 100%
Max SAF RPM= 2600
ECM Status= _________
1
1
2