CONNECTOR INSTALLATION ON THE BUSHING

1 Clean and lubricate* lightly both
bushing interface and elbow connector
interface.
2 Place the elbow connector firmly down
on the bushing &.
3 Insert bail into the bushing tabs and
position bail over elbow connector é.

Installation hint :

Apply a small dash of silicone grease on the
connector's surface to easily snap the bail
into position.
4 Connect earthing lead of the connector and flexible braid to the system earth.
NOTE :
A connector/bushing mated combination should not be allowed to carry the full weight of the cable.
Therefore it is necessary to clamp the cable as close as possible to the connector.

IMPORTANT NOTES :

- Never disconnect the connector from energised equipment nor energise a disconnected connector
without previously installing an appropriate mating part.
- Do not allow hydrocarbon oils or solvents to contaminate the E.P.D.M. rubber.
In the event of contamination, wipe the surface clean with a dry cloth.