IS97180-ENG - K800PB/G-CW45-CA0
18 November 2019 - Revision 2
CAUTION : Read instructions thoroughly and completely prior to beginning installation.
Installation instructions for separable coupling connector
For installation on a 480TB, 484TB or 489TB tee connector or a
Only to be used on copper wire screened cable with extruded semi-conductive screen
For installation on a 480TB, 484TB or 489TB tee connector or a 800PB, 804PB
or 809PB coupling connector tightened with a clamping screw (type 1)
- Supersedes edition of
K800PB/G
800PB, 804PB or 809PB coupling connector.
and conductors of copper or aluminium.
clamping
screw
OR tightened with a stud and flange nut (type 2)
OR
M16
flange nut
This product should be installed only by competent personnel trained in good safety practices involving
high voltage electrical equipment. These instructions are not intended as a substitute for adequate
training or experience in such safety practices. These instructions do not attempt to provide for every
possible contingency. Failure to follow these instructions could result in damage to the product and
serious or fatal injury. IMPORTANT : Cable and associated apparatus must be de-energised, locked out,
and tagged prior to product installation.
28 September 2018
Up to 24 kV
OR
Page 1 of 14
clamping
screw
M16
flange nut