SMC Networks ZSE20B Operation Manual page 39

Digital pressure switch
Hide thumbs Also See for ZSE20B:
Table of Contents

Advertisement

●Auto-preset
When auto-preset is selected in function selection mode, the set value can be calculated and memorized
from the measured pressure. Repeating the suction and release of the workpiece to be set for several
times will automatically optimize the set value.
(1) Selection of auto-preset OUT1 mode
Press the
button in measurement mode to display [AP1 REdY].
(If setting of OUT1 is not necessary, select [AP1 REdY], and then press
the
and
buttons simultaneously for 1 second or longer.
The display will move to [AP2 REdY]).
(2) Preparation of equipment for OUT1
Prepare the equipment for which the pressure of OUT1 is to be set.
(3) Setting of auto-preset for OUT1
Press the
button, [AP1 RUn] will be displayed.
Measurement starts. Operate the device to change the pressure.
(If the
and
longer while [AP1 RUn] is displayed, measurement will be stopped and
[AP2 REdY] will return).
(4) Selection of auto-preset OUT2 mode
Press the
button to set [P_1],[H_1] ([n_1],[H_1] in reverse output mode) to display [AP2 REdY].
(If the setting of OUT2 is not necessary, press the
or longer after [AP2 REdY] display. The display will move to measurement mode).
(5) Preparation of equipment for OUT2
Prepare equipment for which the pressure of OUT2 is to be set, and set the value of OUT2 as in OUT1.
[AP2 RUn] will be displayed and measurement will start.
(If the
and
displayed, measurement will be stopped and measurement mode will return).
(6) Complete setup
Press the
button to set the set value of [P_2] and [H_2] and complete the auto-preset mode. Then,
measurement mode returns.
([n_2], [H_2] in reverse output mode.)
The settings in auto-preset will be as follows in OUT1.
•Normal output
P_1 = A - (A - B)/4
H_1 =  (A - B)/2
In the OUT2 setting, the above P_1, n_1 and H_1 will be P_2, n_2 and H_2 respectively.
If setting is not necessary press the
buttons are pressed simultaneously for 1 second or
buttons are pressed simultaneously for 1 second or longer while "AP2 RUn" is
•Reversed output
n_1 = B + (A - B)/4
H_1 =  (A - B)/2
and
and
buttons simultaneously for 1 second
buttons simultaneously for 1 second or longer.
-38-
A = Maximum pressure
B = Minimum pressure
No.PS※※-OMU0006-A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zse20bfIse20b

Table of Contents