ESIE09-08B
After evacuating the system for 2 hours, pressurize the system to 0.05 MPa (vacuum break)
with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to –100.7
kPa (vacuum drying). If the system cannot be evacuated to –100.7 kPa within 2 hours, repeat
the operation of vacuum break and vacuum drying.
Then, after leaving the system in vacuum for 1 hour, confirm that the vacuum gauge does not
rise.
If the indoor unit is changed by another indoor unit, do the above described leaktest again.
1.3

Additional Refrigerant Charge

 Refrigerant cannot be charged until field wiring has been completed.
 Refrigerant may only be charged after performing the leak test and the vacuum drying (see
 When charging a system, care shall be taken that its maximum permissible charge is never
 Charging with an unsuitable substance may cause explosions and accidents, so always
 Refrigerant containers shall be opened slowly.
 Always use protective gloves and protect your eyes when charging refrigerant.
 When performing service on the unit requiring the refrigerant system to be opened,
 When the power is on, please close the front panel when leaving the unit.
To avoid compressor breakdown. Do not charge the refrigerant more than the specified
amount.
 This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe
 In case re-charge is required, refer to the nameplate of the unit. The nameplate states the
Precautions when recharging/adding R-410A & recharging R-134a
Be sure to charge the specified amount of refrigerant in liquid state to the liquid pipe.
Since this refrigerant is a mixed refrigerant, adding it in gas form may cause the refrigerant
composition to change, preventing normal operation.
 Before charging, check whether the refrigerant cylinder is equipped with a siphon tube or
 Filling using a cylinder with a syphon attached.
 Remark for R-134a: Never recharge more than mentioned on factory name plate.
Test Operation
pipe (if piping work is carried out during the raining season or over a long period of time,
rainwater may enter the pipe during work).
above).
exceeded, in view of the danger of liquid hammer.
ensure that the appropriate refrigerant (R-410A) is charged for outdoor unit, use (R-134a) for
indoor unit.
refrigerant must be evacuated according to local regulations.
lengths some systems require additional charging of refrigerant.
type of refrigerant and necessary amount.
not.
Charge the liquid
refrigerant with the cylinder
in upright position.
Charge the liquid
refrigerant with the cylinder
in up-side-down position.
Test Operation
73