Field Setting From Outdoor Unit - Daikin ALTHERMA HT Service Manual

Hide thumbs Also See for ALTHERMA HT:
Table of Contents

Advertisement

Field Setting
3.2

Field Setting from Outdoor Unit

Caution
Capacity Setting after changing the main outdoor PC Board (A1P) to spare parts PC Board
When you change the main PC Board (A1P) to spare parts PC Board, please carry out the
following setting.
Please Attach the Capacity Setting Adapter corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adapter
106
Capacity Class
1
CAPACITY SETTING ADAPTER (for 11kW/J112)
4 (112)
2
5 (140)
CAPACITY SETTING ADAPTER (for 14kW/J140)
3
6 (160)
CAPACITY SETTING ADAPTER (for 16kW/J160)
Position of Attaching the Capacity Setting Adapter
ERRQ 011/014/016 AAY1
ERSQ 011/014/016 AAY1
ERRQ 011/014/016 AAV1
ERSQ 011/014/016 AAV1
Note
X51A
ESIE09-08B
X51A