WISE Colibri Ceiling

Technical data

Output (ERP):
Frequency band:
Temperature sensor:
Pressure sensor:
IP class:
Corrosivity class:
Air tightness class, casing:
Running time open/close:
Ambient temperature
Operation:
Storage:
RH:
CE marking:

Electrical data

Power supply:
Connections pipe dim.
Power:
Valve actuator:
Max. power consumption:
Variant
Default
+1 valve actuator +2 valve actuator
Ø160, Ø250
8
8
Swegon reserves the right to alter specifications.
50 mW
2.45 GHz, IMS band
(2400--2483 MHz)
0 - 50°C ± -0.5°C
0 - 300 Pa
IP20
110 s
0 – 50°C
-20 – +50°C
10 - 95%
(non condensing)
2016/42/EC (MD)
2014/53/EU (RED)
2011/65/EU (RoHS)
24V AC ±15% 50 - 60Hz
Push-in spring force connections,
max. 2.5 mm
Push-in spring force connections,
max. 1.5 mm
See table below
VA
15
22

Declaration of Conformity

Swegon AB hereby affirms that
WISE Colibri C with integrated radio, complies with the
essential characteristic demands and relevant regulations
specified in the following directives: 2006/42/EC (MD),
2014/53/EU (RED) and 2011/65/EU (RoHS2):
C3
The following standards have been observed:
C
EN ISO 12100:2010
EN 60204-1:2006
EN 60730-1:2011
EN 60730-2-14:2009
IEC 60529:1992+A2:2013
EN 61000-6-2:2007
EN 61000-6-3:2007
EN 300328 V1.9.2, V1.9.1,
V1.8.1
2
2
Person responsible for this declaration:
Name: Ingvar Hagström, Factory Manager Tomelilla
Address: Industrigatan 5, 273 21 Tomelilla, Sweden
Date: 170131
This declaration is applicable only if the product has been
installed according to the instructions in this document and
if no modifications or changes have been made on this
product.
References
www.swegon.com
Building Materials Declaration
WISE Colibri C product data sheet
WISE System Guide
SuperWISE II / SuperWISE II SC User Manual
WISE Project Planning Guide VS & Cooling, Electric &
Control and Ventilation
20181012
Safety of machinery - General principles for
design - Risk assessment and risk mitigation
Safety of machinery - Electrical equipment of
machines - Part 1: Generic standards
Automatic electrical controls for household
and similar use - Part 1: Generic standards
Automatic electrical controls for household
and similar use - Part 2: Particular require-
ments for electric actuators
Degrees of protection provided by enclosures
(IP code)
Electromagnetic compatibility (EMC). Generic
standards. Immunity for industrial environ-
ments
Electromagnetic compatibility (EMC). Generic
standards. Emission standard for residential,
commercial and light-industrial environments
Electromagnetic compatibility and Radio
spectrum Matters (ERM) - Wideband Trans-
mission systems - Data transmission

Advertisement

Table of Contents
loading

Table of Contents