Installation; Mounting The Enclosure - Raypak TempTracker mod+ Hybrid Installation And Operation Instructions Manual

Condensing and non-condensing hybrid control
Table of Contents

Advertisement

10
Raypak, Inc.

InstallatIon

Each of the TempTracker mod+ Hybrid or Extension consists of three primary enclosure components.
• T he Enclosure Display Module: contains the control electronic board, display, buttons, LEDs and electric wiring terminals. It has
two screws to hold it to the base. A program configuration switch, used to adjust the control settings, is placed above the terminals.
This switch is enclosed with the enclosure wiring cover for security. Wiring terminals are of the plug-in type to ease installation and
removal.
• T he Enclosure Base: contains the holes to mount and hold the control against the wall or any flat surface. All other enclosure
components mount on the base. The bottom section of the Enclosure Base contains the wiring chamber with knockouts on the
bottom to ease installation.
• T he Enclosure Wiring Cover: seals the wires from the external environment. It has two screws to hold it the base and a hole to
secure a lock on the wiring enclosure. A plastic web that separates the wiring chamber into high and low volt sections has been
provided.

MountInG tHe enclosure

• Select a location near the equipment to be controlled.
• The surface should be flat and sufficiently wide and strong to hold the TempTracker mod+ Hybrid or the Extension.
• Keep the control away from extreme heat, cold, or humidity. Ambient operating temperature is from 20 to 120°F.
• Remove the Enclosure Wiring Cover from the control enclosure by removing the two bottom screws.
• Remove the Enclosure Display Module by removing the enclosure middle screws.
• Screw the Enclosure Base to the surface through the upper and lower mounting holes on the back of the enclosure.
• Replace the Enclosure Display Module and replace the enclosure middle screws.
• Do not replace the enclosure wiring cover until all wiring is done.
• When purchasing a padlock for the enclosure, the maximum shank diameter should not exceed ¼"
Enclosure Display Module
Enclosure Wiring Cover
Enclosure Base
Hole for optional lock
(not supplied)
Mounting Holes
Display Mounting Screws
Mounting Screws
Wiring Cover