Daikin Magnitude Installation, Operation And Maintenance Manual page 57

Magnetic bearing centrifugal chillers 125 to 400 tons (440 to 1400 kw) hfc-134a refrigerant 50/60 hz

Advertisement

Possible Alarms and Events
There are three types of alarms: faults, problems, and warnings. In addition to these three alarms, there are also "events." See
the following tables for examples of faults, problems, warnings, and events that can occur. Separate tables are shown based on
whether the alarm source is the unit or the compressor.
NOTE: In the "Alarm Reset" column of the following tables, itallics indicate special alarm conditions or severity. If the "Alarm
Reset" says "Auto-clears," it indicates that the alarm will auto-clear after the condition is resolved and the normal
condition returns.
Fault Alarms
Equipment protection faults cause rapid compressor shutdown. The compressor is stopped immediately (if the compressor was
running).
Table 18: Unit Fault Alarms
Description
Low Motor Current Comp 1
Low Motor Current Comp 2
No Condenser Water Flow
No Compressor Stop Comp 1
No Compressor Stop Comp 2
No Evaporator Water Flow
Low Suction pressure Comp 1
Low Suction pressure Comp 2
Leaving Evaporator Water Temperature Sensor Fault Comp 1
Surge High Suct SH-Running Comp 1
Surge High Suct SH-Running Comp 2
Expansion Alarm – FAULT (external alarm)
Check Valve Fault 1
Check Valve Fault 2
Table 19: Compressor Fault Alarms
Description
Compressor Current Overload Trip #1
Compressor Current Overload Trip #2
High Motor Temperature Comp 1
High Motor Temperature Comp 2
Overvoltage On Compressor 1
Overvoltage On Compressor 2
Undervoltage On Compressor 1
Undervoltage On Compressor 2
High Discharge pressure Comp 1
High Discharge pressure Comp 2
High Discharge Temperature Comp 1
High Discharge Temperature Comp 2
Starter Fault Compressor 1
Starter Fault Compressor 2
www.DaikinApplied.com
HMI Alarm Message
COMPR STOP - Motor Current Low
COMPR STOP - Motor Current Low
COMPR STOP - Condenser Water Flow Loss
COMPR STOP - Current High with Compr OFF
COMPR STOP - Current High with Compr OFF
COMPR STOP - Evaporator Water Flow Loss
COMPR STOP - Suction pressure Low
COMPR STOP - Suction pressure Low
COMPR STOP - Evap LWT Sensor Out of Range
COMPR STOP - Surge Temperature
COMPR STOP - Surge Temperature
COMPR STOP - Control Fault (External Input)
CHILLER STOP - Check Valve Failure
CHILLER STOP - Check Valve Failure
HMI Alarm Message
COMPR STOP - Motor Current Overload
COMPR STOP - Motor Current Overload
COMPR STOP - High Motor Temperature
COMPR STOP - High Motor Temperature
COMPR STOP - Line Voltage High
COMPR STOP - Line Voltage High
COMPR STOP - Line Voltage Low
COMPR STOP - Line Voltage Low
COMPR STOP - Discharge pressure High
COMPR STOP - Discharge pressure High
COMPR STOP - Discharge Temperature High
COMPR STOP - Discharge Temperature High
COMPR STOP - Compressor Fault
(previously used for WMC general compressor fault)
COMPR STOP - Compressor Fault
(previously used for WMC general compressor fault)
55
IOM 1210-7 • MAGNITUDE
o
peraTIon
Alarm Reset
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Locked off (requires local reset)
Locked off (requires local reset)
Alarm Reset
Auto-clears
Auto-clears
Locked off if UL Limit is exceeded
Auto-clears
Auto-clears
Locked off if Tripped 3x in 50 min
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Auto-clears
Locked off if Tripped 3x in 50 min
Auto-clears
Locked off if Tripped 3x in 50 min
Auto-clears
Locked off if Tripped 3x in 50 min
Auto-clears
Locked off if Tripped 3x in 50 min
Reset is dependent on specific alarm
Reset is dependent on specific alarm
MODEL WMC CHILLERS
®