Figure 59: Active Alarms Screen
IOM 1210-7 • MAGNITUDE
MODEL WMC CHILLERS
®
The current active alarms (there may be more than one) will be
displayed on the Active Alarms Screen. Alarms are arranged
in order of occurrence, with the most recent on top. The date/
time and cause of the alarm are displayed. See the
Alarms and Events"
section starting on
on alarms that may occur.
After eliminating the cause of the alarm, clear the alarm by
pressing the CLEAR button. This will clear the alarm from
the register and allow the unit to restart after going through
the start sequence. The alarm notice will be deleted from the
screen.
If the cause of the alarm is not remedied, the alarm is still
active and the alarm message will remain open. The unit will
not begin its starting sequence.