TIMERS Setpoints
Figure 31: TIMERS Setpoint Screen
Table 10: TIMERS Setpoint Settings
Description
Default
Full Load Timer
300 sec
Interlock Timer
10 sec
Stop-Start Timer
Start-Start Timer
Evap Recirculate Timer
30 sec
Evaporator Trip Time
12 sec
Condenser Trip Time
20 sec
NOTE: In
Table 10
and in the rest of the Setpoint tables on the following pages, the letters in the Password column refer to the
following:
• O = Operator Level (The password number for operator level is 100.)
• M = Manager Level (The password number for manager level is 2001.)
• T = Technician Level (the password number for technician level is only provided to technicians who have completed
Service training with the Daikin Learning Institute.)
IOM 1210-7 • MAGNITUDE
Range
Password
0 to 999 sec
10 to 240 sec
3 min
1 to 20 min
5 min
2 to 60 min
0.2 to 5 min
1 to 20 sec
1 to 20 sec
MODEL WMC CHILLERS
®
Time compressor must load (without unloading) before vanes are considered fully
M
open. This setpoint does not apply to this model chiller.
T
Maximum time allowed before interlock confirmation from compressor
M
Time from when compressor stops to when it can restart
M
Time from when compressor starts to when it can start again
M
Time that evaporator pump must run before compressor start
M
Sets the suction pressure trip point if the pressure rises within 5psi
M
Sets the discharge pressure trip point if the pressure rises within 5psi
36
o
Comments
www.DaikinApplied.com
peraTIon