Download Print this page

Daikin Magnitude Installation, Operation And Maintenance Manual page 15

Magnetic bearing centrifugal chillers 125 to 400 tons (440 to 1400 kw) hfc-134a refrigerant 50/60 hz

Advertisement

Compressor Dimensions
The compressor dimensions on all WMC models are the same.
The dimensions are shown in
Figure 11: Compressor Dimensions for all WMC Models
WIDTH
20.4 in (518 mm)
LENGTH
31.0 in (788 mm)
NOTE: Compressor mounting bolts are removable.
Component
E3012 Evaporator
C2612 Condenser
E2209 Evaporator
C2009 Condenser
E2212 Evaporator
C2012 Condenser
E2609 Evaporator
C2209 Condenser
E2612 Evaporator
C2212 Condenser
E3009 Evaporator
C2609 Condenser
Compressor
* Component weights based on unit with standard tube configuration
www.DaikinApplied.com
Figure 11
HEIGHT
18.9 in (479 mm)
Dry Weight
LBS
KG
5075
2299
3900
1767
2708
1227
2230
1010
3071
1391
2677
1213
3210
1454
2511
1137
3880
1758
3031
1373
4397
1992
3210
1454
330
150
Compressor Rigging Requirements
To properly rig the compressor, attach a sufficient chain hoist
to each compressor eyebolt. (There is one eyebolt at each end
of the compressor.) Use a spreader bar between the two chain
hoists, as shown in
Figure
Figure 12: WMC Compressor Rigging Setup
NOTE: The spreader bar in
only and may not reflect the appearance of the actual
spreader bar needed.
Compressor Removal and Re-
Attachment Instructions
Follow the steps listed to remove and re-attach the
compressor.
Compressor Removal Preparation
1. Close the shutoff valve at condenser liquid line outlet.
2. Close all other related shut-off valves.
3. Evacuate the refrigerant charge from the unit.
4. Ensure that the charge has been removed from the
compressor and evaporator and that the discharge check
valve is holding the charge in the condenser.
5. Loosen and remove bolts on the compressor discharge
and suction flanges (see
6. Disconnect motor cooling line and seal openings on both
compressor and tubing.
7. Cover openings to prevent foreign objects from entering.
8. Disconnect control cable from J6 on IO board in
MicroTech panel. Cable will remain connected to the
compressor.
9. Disconnect power cables from compressor power
terminals
Compressor Removal
1. Loosen and remove bolts on the suction elbow to
butterfly valve flange. Remove suction elbow and install
a flange cover on the valve.(see
13
IOM 1210-7 • MAGNITUDE
I
nsTallaTIon
12, to safely lift the compressor.
Figure 12
is a representation
Figure 13, flag #2 and
#3).
Figure 13, flag
#6).
MODEL WMC CHILLERS
®

Hide quick links:

Advertisement

loading