Daikin Magnitude Installation, Operation And Maintenance Manual page 47

Magnetic bearing centrifugal chillers 125 to 400 tons (440 to 1400 kw) hfc-134a refrigerant 50/60 hz

Advertisement

MOTOR Setpoint Screen
Figure 47: MOTOR Setpoint Screen
Table 15: MOTOR Setpoint Settings
Description
Nominal Capacity
Maximum LWT Rate
0.5 °F/min
Minimum LWT Rate
0.1 °F/min
Soft Load Ramp Time [SP7]
Initial Soft Load Limit [SP6]
Soft Load Enable [SP5]
Nameplate RLA * [SP4][
Maximum Amps
Minimum Amps
Demand Limit Enable
Harmonic Filter On Threshold
Harmonic Filter Off
IGV Lead Start
IGV Lag Start
Lead Start Speed
Lag Start Speed
NOTE: Setpoints that have a technician level password (T) should only be changed by a Daikin Applied technician. Contact a
Daikin Applied service representative for more information.
www.DaikinApplied.com
Default
Range
Password
100
0 to 9999 Tons
0.1 to 5.0 °F/min
0.1 to 5.0 °F/min
5 min
1 to 60 min
40%
10 to 100%
OFF
OFF, ON
Dependent on dataplate
100%
10 to 100%
40%
5 to 80%
OFF
OFF, ON
30%
10-100%
15%
10-100%
12%
0 to 100%
40%
0 to 100%
25%
0 to 100%
0%
0 to 100%
* Chiller Nameplate RLA MUST match chiller dataplate per compressor.
T
Determines when to shut off a compressor. ONLY applies to multi-chiller setup.
M
Inhibits loading if LWT change exceeds the setpoint value
M
Additional compressor can start if LWT change is below setpoint
M
Time period to go from initial load point (% RLA) set in SP5 to 100% RLA
M
Initial amps as % of RLA, Uses SP4 & 6
M
Soft load on or off, Uses SP6 & 7
T
T
% RLA above which loading is inhibited (Load Limit) SP + 5% unloads compressor
T
% RLA below which unloading is inhibited
ON sets %RLA at 0% for 4 mA external signal and at 100% RLA for 20 mA signal
O
M
Min %RLA that the harmonic filter shuts off
M
Harmonic Filter Engages > 06 RLA%
T
IGV Position for lead compressor start.
T
IGV Position for lag compressor start
T
Select percentage of available speed range.
T
Select percentage of available speed range.
CAUTION
45
IOM 1210-7 • MAGNITUDE
Comments
RLA value from chiller data plate
OFF – signal is ignored
MODEL WMC CHILLERS
®
o
peraTIon