Environmental Conditions; Dimensions And Weights - Eaton Power Xpert UX 12 User Manual

With w-vaci circuit breaker (up to 24 kv) air insulated medium-voltage switchgear
Table of Contents

Advertisement

2.4.2

Environmental conditions

During operation
Environment
Ambient temperature
Maximum over 24 hours
Average over 24 hours
Minimum
Altitude at site
Maximum altitude
Humidity
Relative humidity
Maximum over 1 month
Sound level produced
Average
During storage
Environment
2.4.3

Dimensions and weights

Main dimensions (standard model)
Circuit-breaker panel
12 kV and 17.5 kV
UX17 25 kA 630 A
UX17 31.5 kA 1250 A
UX17 40 kA 2000 A
UX17 40/50 kA 2000 A
UX17 40/50 kA 3150 A 1000 mm wide
24 kV
UX24 20 kA 800 A
UX24 25 kA 1250 A
UX24 25 kA 2000 A
UX24 25 kA 2500 A
*: IAC of this panel is 26.3 kA-1s
In accordance with IEC 62271-1 par. 2.1.1,
Limit values below, among others, apply
+40°C (adequate de-rating if higher ambient conditions apply)
+35°C
-5°C
1000 m above sea level (adequate de-rating if higher altitude conditions
apply)
90%
< 70 dBA
In accordance with IEC 62271-1 par. 2.1.1
Depth
600 mm wide
1310 mm
600 mm wide
1310 mm
800 mm wide*
1325 mm
800 mm wide
1500 mm
1500 mm
800 mm wide
1570 mm
800 mm wide
1570 mm
1000 mm wide
1570 mm
1000 mm wide
1570 mm
®
Power Xpert
UX with W-VACi circuit breaker 6063308 G01 01 14 July 2011 www.eaton.com
Width
Height
(C)
(A)
600 mm
2200 mm
600 mm
2200 mm
800 mm
2200 mm
800 mm
2200 mm
1000 mm
2200 mm
800 mm
2320 mm
800 mm
2320 mm
1000 mm
2320 mm
1000 mm
2320 mm
Product description
Height including arc
chamber (B)
2760 mm
2760 mm
2760 mm
2760 mm
2760 mm
2880 mm
2880 mm
2880 mm
2880 mm
23