4.1.1

Mechanical operation door open

When the door is open the circuit breaker or contactor
withdrawable unit can be operated directly from the
controls mounted on the front of the unit. For full
information refer to the individual operations and
maintenance manual.
If the control plug is connected then a full functional test of
the unit is possible.
The door cannot be opened when the unit is in the
Service position. To open the door make sure the
unit is in the OFF position and it is racked out fully to
the TEST position. This will release the door
interlock mechanism and the door can now be
opened.
Door Interlock Defeat Mechanism: To open the door
in an emergency, remove two screws.
4.1.2

Charging the closing spring

For operating of the circuit breaker unit see the user
manual of the W-VACi.
1.
Secondary Connector
2.
Manual Close Button
3.
Closed/Open Indicator
4.
Manual Open Button
5.
Front Panel
6.
Manual Charging Handle
7.
Nameplate
8.
Spring Charged/Discharged Indicator
9.
Operation Counter
NOTE
NOTE
®
Power Xpert
UX with W-VACi circuit breaker 6063308 G01 01 14 July 2011 www.eaton.com
Fig. 4-1 Door Interlock defeat operation
6
7
8
9
Fig. 4-2 Circuit Breaker
System operation
1
2
3
4
5
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power xpert ux 17.5Power xpert ux 24

Table of Contents