Data Format
Scale
Common
Update Rate

Enumerated Status (ENS)

Table 3.4.5.19-1 Configurable ENS properties
Property/Parameter
Basic
Common Data Class
Addresses
Indication Address
Data Format
1 = WORD
2 = Integer
3 = Long MSW First
4 = Long MSW Last
5 = Float MSW First
6 = Float MSW Last
Default: 1
Default: None
0...60000
Default: 0
Value or Value range/Default
ENS
0...65535
Default: 0
1 = WORD
2 = Integer
3 = Long MSW First
4 = Long MSW Last
5 = Float MSW First
6 = Float MSW Last
Default: 1
1MRS756913
Data format for indication
value.
Scale used with indication
value.
Maximum update rate of indica-
tion changes between the OPC
server and the client in milli-
seconds. The value 0 means
that the server sends all the
changes to the client.
Description
Common data class according
to IEC 61850.
Indication address. Holding
register address for the control.
Holding register (4X reference)
address range 40001-49999.
Address 0 equals no informa-
tion available.
Data format for indication
value.