Binary Counter Reading (Bcr) - ABB COM600 series User Manual

Modbus serial slave (opc)
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

3.4.5.5.
28
COM600 series, Version 5.1
Modbus Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Data Format
1 = WORD
2 = Integer
3 = Long MSW First
4 = Long MSW Last
5 = Float MSW First
6 = Float MSW Last
Default: 1
Common
Update Rate
0...60000
Default: 0

Binary counter reading (BCR)

Table 3.4.5.5-1 Configurable BCR properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
BCR
Class
Addresses
Indication Address
0...65535
Default:0
Data Format
1 = WORD
2 = Integer
3 = Long MSW First
4 = Long MSW Last
5 = Float MSW First
6 = Float MSW Last
Default: 1
Common
Description
Data format for write value.
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.
Description
Common data class according to IEC
61850.
Indication address.
Data format for counter value.
1MRS756913