Controllable Integer Status (Inc) - ABB COM600 series User Manual

Modbus serial slave (opc)
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

1MRS756913
3.4.5.11.
COM600 series, Version 5.1
Modbus Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Common
Update Rate
0...60000
Default: 0
Data Specific
Send as Inverse
True
Value
False
Default: False
Send as Single
True
Point
False
Default: False

Controllable integer status (INC)

Table 3.4.5.11-1 Configurable INC properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
INC
Class
Addresses
Control Address
0...65535
Default: 0
Indication Address
0...65535
Default: 0
Data Format
1 = WORD
2 = Integer
3 = Long MSW First
4 = Long MSW Last
5 = Float MSW First
6 = Float MSW Last
Default: 1
Description
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.
Specifies if a value of an indication signal
is sent as an inverse value.
Specifies if a value of an indication signal
is sent as a single point value.
Description
Common data class according to IEC
61850.
Control address.
Indication address.
Data format for indication value.
33