1MRS756913
3.4.5.6.
COM600 series, Version 5.1
Modbus Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Update Rate
0...60000
Default: 0

Binary controlled step position information (BSC)

Table 3.4.5.6-1 Configurable BSC properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
BSC
Class
Addresses
Control Address
0...65535
Default: 0
Indication Address
0...65535
Default: 0
Data Format
1 = WORD
2 = Integer
3 = Long MSW First
4 = Long MSW Last
5 = Float MSW First
6 = Float MSW Last
Default: 1
Scale
Default: None
Common
Update Rate
0...60000
Default: 0
Data Specific
Description
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.
Description
Common data class according to IEC
61850.
Control address.
Indication address.
Data format for position value.
Scale used with position information.
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.
29