Reading/Writing Position Counter Values Through Fieldbus; Configuration Of Htl Encoder Motor Feedback - ABB ACS880 Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

58 Program features
Note: With a multiturn absolute encoder, bit 6 of
drive if the encoder has recovered from the error; bit 4 is not cleared. The status of the
position counter is retained over a control unit reboot, after which position calculation
resumes from the absolute position given by the encoder, taking into account the initial
position specified by 90.58.
WARNING!
If the drive is in stopped state when an encoder error occurs, or if the drive is not
powered, parameters 90.4, 90.5,
movement of the load can be detected. When using previous position values
(90.60
is set to
unreliable if the load is able to move.

Reading/writing position counter values through fieldbus

The parameters of the position counter function, such as
accessed from an upper-level control system in the following formats:
16-bit integer (if 16 bits are sufficient for the application)
32-bit integer (can be accessed as two consequent 16-bit words).
For example, to read parameter
the desired dataset (in group 52) to Other – 90.7, and select the format. If you select a
32-bit format, the subsequent data word is also automatically reserved.

Configuration of HTL encoder motor feedback

1. Specify the type of the encoder interface module (parameter
the slot the module is installed into (91.12).
2. Specify the type of the encoder
from the drive after the value is changed.
3. Specify the interface module that the encoder is connected to
4. Set the number of pulses according to encoder nameplate (92.10).
5. If the encoder rotates at a different speed to the motor (ie. is not mounted directly
on the motor shaft), enter the gear ratio in
6. Set parameter
will automatically revert to Done.
7. Check that
91.2
the status of the module; both LEDs should be glowing green.
8. Start the motor with a reference of eg. 400 rpm.
9. Compare the estimated speed (1.2) with the measured speed (1.4). If the values
are the same, set the encoder as the feedback source
Continue from previous
90.7
(92.1
91.10
to
Refresh
to apply the new parameter settings. The parameter
is showing the correct interface module type (FEN-31). Also check
90.35
is cleared at the next stop of the
90.7
and
90.35
are not updated because no
value), be aware that the position data is
through fieldbus, set the selection parameter of
= HTL). The parameter listing will be re-read
90.43
and 90.44.
90.7
and 90.58, can be
91.11
= FEN-31) and
(92.2
=
Module
(90.41
=
Encoder
1).
1).

Advertisement

Table of Contents
loading

Table of Contents