Download Print this page

Advanced Energy Thyro-PX Anybus Modbus TCP Manual page 16

Advertisement

®
Advanced Energy
Table 11. Parameter list (Continued)
API
Read /
Address
#
Write
Dec
44
Read
4198
45
Read
4200
57010166-00A
Parameter Name
Hex
1066
Device CPU temperature
r
1068
Device error r
Thyro-PX
Type
FLOAT
CPU temperature - read
UINT32
Error - read
Bit 0: Aux. supply error
Bit 1: Parameter error
Bit 2: Frequency error
Bit 3: Internal communication error
Bit 4: Temperature CPU too high
Bit 8: Phase L1 missing
Bit 9: Phase L2 missing
Bit 10: Phase L3 missing
Bit 11: Fuse 1 broken
Bit 12: Fuse 2 broken
Bit 13: Fuse 3 broken
Bit 14: Thyristor 1 short-circuit
Bit 15: Thyristor 2 short-circuit
Bit 16: Thyristor 3 short-circuit
Bit 17: External error 1 (customer-
specific)
Bit 18: External error 2 (customer-
specific)
Bit 19: External error 3 (customer-
specific)
Bit 21: Extension card X53
configuration error
Bit 22: Extension card X54
configuration error
Bit 23: External extension 1
configuration error
Bit 24: External extension 2
configuration error
Bit 25: dASM card configuration error
Bit 26: Anybus configuration error
Bit 27: Internal error
®
Anybus
Modbus TCP
®
Thyro-PX
Anybus
Modbus TCP
Parameter Description
16

Hide quick links:

Advertisement