Interrupts/diagnostics alarms

5.3 Diagnostics alarms

5.3
Diagnostics alarms
Diagnostics alarms
A diagnostics alarm is output for each diagnostics event and the DIAG LED flashes on the
module. The diagnostics alarms can, for example, be read from the diagnostics buffer of the
CPU. You can evaluate the error codes with the user program.
Note
You can connect 2 actuators per output.
The diagnostics of the two actuators influence each other in the case of duplicate wiring.
This means that a single short-circuit affects both actuators.
Table 5- 6
Diagnostics alarms, their meaning and corrective measures
Diagnostics alarms
Error code
Short-circuit
1
1 2
H
Overtemperature
5
H
High limit violated
7
H
Parameter assign-
10
ment error
No load voltage
11
Communications
13
error
Channel temporarily
1F
unavailable
The channels 0 and 1 or 2 and 3 each form a load group. Within a load group, a short-circuit can have an effect on the
1
adjacent channel. The load groups do not have an effect on each other in the case of a short-circuit.
If the short-circuit persists, the module heats up. This may trigger temperature monitoring with overtemperature
2
diagnostic interrupt.
32
Meaning
Short-circuit of the actuator supply
The module has detected that the maximum
permitted module temperature has been
exceeded. All channels of the module are
switched to high resistance. The module is
then restarted.
The permitted value range of the duty factor
has been exceeded.
The module cannot evaluate parameters
H
for the channel.
Incorrect parameter assignment.
No or insufficient supply voltage L+
H
Module is defective.
H
Firmware update in progress or update has
H
been canceled.
The module does not read out any process
values or substitute values in this state.
Solution
Correct the process wiring
Correct the process wiring
Correct the output value (0 to 1000)
Correct the parameter assignment
Check supply voltage L+ on the
BaseUnit
Check BaseUnit type
Replace the module.
Wait for firmware update.
Restart the firmware update.