Codes for time period of the pulse width modulation
The table below contains the codes for the time period of the pulse width modulation of the
digital output module. You must enter these codes in bytes x+6 and x+7 of the channel
parameter block of data record 128 (see previous figure).
Table A- 1
Value
4
7
12
14
21
26
30
33
36
Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
Manual, 03/2015, A5E34944434-AA
A.1 Parameter assignment and structure of the parameter data record
Codes for output range
Time period
0.20 ms
0.40 ms
0.93 ms
1.33 ms
4.27 ms
10.67 ms
21.33 ms
34.13 ms
59.73 ms
Parameter data record
Code
0000 0100
0000 0111
0000 1100
0000 1110
0001 0101
0001 1010
0001 1110
0010 0001
0010 0100
43