Siemens SENTRON PAC3200T Product Manual page 59

Measuring devices 7km
Hide thumbs Also See for SENTRON PAC3200T:
Table of Contents

Advertisement

Power supply
Power supply
Design of the power supply
Work area
Power consumption
Overvoltage category
Digital Input
Digital Input
Number
Type
Maximum switching voltage
Input current
Digital output
Digital output
Number
Type
Design/function
Maximum switching voltage
Output current
Internal resistance
Overvoltage category
Pulse output function
Max. switching frequency
Short-circuit protection
PAC3200T
Manual, 04/2017, L1V30415168B-01
"1" signal detection
"0" signal detection
For signal "1"
Continuous load
Transient overload
For signal "0"
Standard for pulse emitter
Adjustable pulse duration
Min. settable time frame
Wide range AC / DC power supply
110 V - 250 V ±10 %
5 VA
CAT III
1
Passive
30 V
2.5 ... 10 mA
≤0.5 mA
1
Passive
Switching output or pulse output
30 V
Depends on the load and the external power
supply
≤50 mA (thermal overload protection)
≤130 mA for 100 ms
≤0.2 mA
30 Ω
CAT I
Signal characteristics in accordance with
IEC 62053-31
30 ... 500 ms
10 ms
17 Hz
Yes
Technical data
9.1 Technical data
59