Commissioning
6.3 Parameterizing the device
USAGE TYPE
UNIT
PULSES PER UNIT
INPUT PULSE DIVIDER
46
Usage type of the digital input.
Not used: Digital input is deactivated.
Count input pulses: Counting of input pulses.
Note: The universal counter must also be parameterized
for pulse counting. Set the parameter "Ad-
vanced > Universal Counter" to "Digital Input".
High tariff/low tariff switchover: Switching between tariffs.
Low tariff if input active.
Demand synchronization: Synchronization of power de-
mand.
Default setting: Not used
The "UNIT" property is only visible if "Count input pulses" is set
for the "USAGE TYPE".
Countable unit with pulse counting:
• Active Energy (kWh)
• Reactive Energy (kvarh)
The "PULSES PER UNIT" property is only visible if "Count input
pulses" is set for the "USAGE TYPE".
Range: 1 to 4000
Default setting: 1
The "INPUT PULSE DIVIDER" property is only visible if "Count
input pulses" is set for the "USAGE TYPE".
Range: 1; 10; 100; 1000
Default setting: 1
Formula:
Example:
Pulses per unit: 50
Input pulse divider: 100
Unit: kWh
PAC3200T
Manual, 04/2017, L1V30415168B-01