Connection
5.3 Connection examples
(8) Three-phase measurement, three conductors, unbalanced load, with voltage transformer,
with two current transformers
Connection type 3P3W
*
**
***
Figure 5-9
(9) Three-phase measurement, three conductors, balanced load, without voltage
transformer, with one current transformer
Connection type 3P3WB
*
**
***
Figure 5-10
30
Fuses must be provided by the customer.
for V
, V
, V
: 10 A
1
2
3
for L/+: 1 A
Connection of supply voltage
Grounding optional
Connection type 3P3W, with voltage transformer, with two current transformers
Fuses must be provided by the customer.
for V
, V
, V
: 10 A
1
2
3
for L/+: 1 A
Connection of supply voltage
Grounding optional
Connection type 3P3WB, without voltage transformer, with one current transformer
PAC3200T