CTT Timer
Signal On Delay 2
Signal On Delay 2 ( Sond2 )
With power applied to the CTT, the leading edge of the input
signal at START will begin the timing period setting value SV
(timing up or down based on parameter ( t modE ) or by DIP
switch 2). At the end of the timing period both outputs will turn
ON momentarily for the time set in the output pulse width param-
eter ( tout1 ) or will be maintained ON if the output pulse width
parameter ( tout1 ) is set to 0.00. The trailing edge of the "start"
signal will turn OFF the outputs and reset the timing period.
The leading edge of a "reset" input signal at RST1 will turn
OFF the outputs and reset the timing period. The "reset" signal
minimum pulse width is set by reset pulse width parameter
( rtSr ) or DIP Switch 8.
The leading edge of a "pause" input signal at GATE will pause
the timing period after it has been started. The timing period
will continue after the trailing edge of the external switch "pause"
(Gate) signal.
When power is removed, both outputs will turn OFF and the
timing period will be reset.
Gate
Input
(Optional)
0V
CP1
Start
11
12
Input
RST2/
+12V
RST1
6
7
Reset
+VDC
0VDC
Externally Powered
OUT1
SPST
DIP Switch Set Up of the CTT Parameters:
Dip Switch Settings - Table 1
Switch Function
Off
1
Dip switch
Disabled
Counting
2
Timer mode
up
3
Output
See Output Mode Table
- Table 2
mode
4
5
Displayed
See Display Units Table
6
unit
- Table 3
7
Reset signal
8
20 ms
pulse width
3-6
Digital Counter / Timer / Tach User Manual, 1st Ed.
Timer Wiring Examples
PNP
INPUTS
Gate
Input (Optional)
CP2/
0V
CP1
GATE (Pause)
13
11
12
Start
L-
START
+12V
RST1
L+
8
6
7
Reset
Internally Powered
Load
15
14
15
OUT1
NPN/
SINKING
10
9
10
Load
Output Mode - Table 2
Switch 3
On
OFF
Enabled
ON
Counting
down
OFF
ON
1 ms
Power signal
Start signal
Pause signal
Reset
Output signal
SV
Up
SV
Down
Gate
Input (Optional)
CP2/
CP2/
0V
CP1
GATE (Pause)
GATE (Pause)
13
11
12
13
Start
RST2/
RST2/
START
+12V
RST1
START
8
6
7
8
Reset
Internally Powered
Outputs
OUT2
NPN/
SINKING
OUT2
1
2
3
+VDC
SPDT
Load
Load
0VDC
Switch 4
Output Mode
OFF
Sond1
OFF
Sond2
ON
Soffd
ON
Son
t
0
0
Signal On Delay 2
NPN
INPUTS
Gate
Input
(Optional)
0V
CP1
11
12
Start
L-
Input
+12V
RST1
L+
6
7
Reset
+VDC
0VDC
Externally Powered
1
2
3
Load
+VDC
0VDC
Display Units - Table 3
Switch 5
Switch 6
Switch 7 Display Units
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
1 - 8 0 0 - 6 3 3 - 0 4 0 5
t
CP2/
GATE (Pause)
13
RST2/
START
8
0.01 sec.
0.1 sec.
1 sec.
min., 0.01 sec.
min., 0.1 sec.
0.1 min.
minute
hr., min., sec.