Installation

Floor Mounting Manifold Control

For floor mounting manifold control
panel, a manifold control stand kit and an
appropriate number of manifold header
stand kits should be ordered separately.
One manifold control panel stand kit
contains all items needed to mount control
panel. Depending upon number of header
extensions on right side of manifold, one or
more header stand kits are required.
A vertical channel is required for each
right side header extension. Each header
stand kit contains two vertical channels and
all necessary items to support two header
extensions.
Verify contents of manifold control stand
and header stand kits (Figures 10 and 11):
1. Remove manifold control panel from
shipping carton and place face down on
foam packaging insert.
2. Mounting bracket is shipped attached to
back of manifold control panel. Remove
lower 3/8" mounting nut as shown in
Figure 1. Pull bottom of bracket away
from manifold control panel and slide
bracket off two upper control panel
mounting bolts.
3. Only bracket will be needed at this time.
Set manifold control panel aside for
installation later.
NOTE:
Return manifold control panel to shipping
carton if necessary to protect and keep it
clean.
4. Attach post base to one end of each 80-
inch channel as shown in Figure 12,
Detail A. Use two each 3/8" bolts, flat
washers and channel nuts per base.
Tighten all four bolts.
12
Part No. 6-847703-00 Rev. C00
Figure 10
Figure 11
5. Stand each channel / base side by side.
Attach manifold mounting bracket to both
bases as shown in Figure 12, Detail B. Use
four each 3/8" bolts, flat washers and channel
nuts per base. Top of bracket should be level
and positioned 79 3/4" above floor. Tighten all
four bolts.
6. Position entire assembly in desired manifold
mounting location. Mark location of eight base
mounting holes. Move assembly aside and
drill holes. Minimum 3/8" diameter mounting
bolts are recommended (by others).
7. Reposition assembly over holes and install
mounting hardware (by others). Tighten all
mounting bolts.