Parameters Of The "Expert Level With Diagnostics And Test - Siemens RDF301 Basic Documentation

Semi-flush mount communicating room thermostats
Hide thumbs Also See for RDF301:
Table of Contents

Advertisement

Name
Expert level
P30
Heat P-band Xp /
switching diff
P31
Cool P-band Xp /
switching diff
P33
Dead zone Comfort mode
P34
Setpoint differential
Integral action time Tn
P35
P36
H/C ch'over swi point
cooling
H/C ch'over swi point
P37
heating
P38
Input X1
RDF301.....
(range 0..8)
RDF600KN
(range 0..10)
P39
Normal position input X1
P40
Input X2
RDF301.....
(range 0..8)
RDF600KN
(range 0..10)
P41
Normal position input X2
P44
Actuator running time
Y11/Y21
P45
RDF600KN:
Power of electric heater
on Y21 (for adaptive
temperature
compensation
P46
Output Y11/Y21
P48
ON time minimum 2-pos
output
OFF time minimum 2-pos
P49
output
P50
Purge time
Siemens
Building Technologies
3.14.4 Parameters of the "Expert level
with diagnostics and test"
Factory setting
2 K
1 K
2 K
2 K
RDF301... /
5 min
RDF600KN
45 min
16 °C
28 °C
3 = Op mode contact,
window contact
5)
0 (N.O.)
1 = Ext. sensor
5)
0 (N.O.)
150 s
0.0 kW
ON/OFF (1)
1 min.
1 min.
OFF
RDF301, RDF301.50..., RDF600KN, RDF600KN/S
Range
0.5 ... 6 K
0.5 ... 6 K
0.5 ... 5 K
0.5 ... 5 K
0...10 min
0...120 min
10...25 °C
27...40 °C
0 = --- (no function)
1 = Room temp ext. sensor /
Return air temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact,
Window contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)
8 = Monitor input (Temp)
10: Presence detector (DI)
0 = Normally open
/ Open
1 = Normally closed / Close
0 = --- (no function)
1 = Room temp ext. sensor /
Return air temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact,
Window contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)
8 = Monitor input (Temp)
10: Presence detector (DI)
0 = Normally open
/ Open
1 = Normally closed / Close
20...300 sec
0.0...1.2 kW
0 = 3-position
1 = ON/OFF
1...20 min
1...20 min
OFF:
Not active
1...5 min: Active with selected
duration
Basic Documentation
Appl.
Appl.
x
P46
x
P46
P38, P40
P38, P40
P38
P40
P46
x
Appl.
P46
P38, P40
71 / 94
CE1P3171en
2017-12-07