Zone Addressing In Lte Mode (In Conjunction With Synco) - Siemens RDF301 Basic Documentation

Semi-flush mount communicating room thermostats
Hide thumbs Also See for RDF301:
Table of Contents

Advertisement

Engineering and
commissioning
Note:
Siemens
Building Technologies
∂ For a detailed description of KNX (topology, bus supply, function and setting of
LTE zones, filter tables, etc.), see "Communication via the KNX bus for Synco
700, 900 and RXB/RXL, Basic Documentation" [6].
∂ LTE Mode data points and settings are described in the Synco Application
Manual [12].
∂ To engineer and commission a specific system, use the Synco700 planning and
commissioning protocol (XLS table in HIT, [7]).
3.11.3 Zone addressing in LTE Mode (in conjunction with
Synco)
In cases where RDF KNX room thermostats are used in LTE Mode (e.g. in
conjunction with Synco), zone addresses need to be allocated.
The following zone address must be defined together with the Synco devices at the
planning stage depending on the application.
Short description
Geographical zone (apartment)
Geographical zone (room)
Heat distr zone heating coil
Refr distr zone cooling coil
"Subzone" of "Geographical zone" is fix 1 (not adjustable).
The device will send and receive LTE communication signals only if the zone
address is valid (not OSV = out of service).
RDF301, RDF301.50..., RDF600KN, RDF600KN/S
Factory setting
--- (out of service)
1
1
1
Basic Documentation
Parameter
P82
P83
P84
P85
55 / 94
CE1P3171en
2017-12-07