Application mode

#
0
1
2
3
4
5
6
8
9
36 / 94
Siemens
Building Technologies
3.6.2
Application mode
The behavior of the thermostat can be influenced by a building automation
The behavior of the
control system
system (BACS) via bus with the command "Application mode
With this signal
this signal, cooling and/or heating activity can be enabled or disabled.
cooling and/or heating activity can be enabled or disabled.
Application mode is supported in LTE Mode and S-Mode.
Application mode is supported in
The RDF KNX thermostats
KNX thermostats support the following commands:
Application
Description
mode
Auto
Thermostat automatically changes between
heating and cooling
Heat
Thermostat is only allowed to heat
Morning
If "Morning warm-up" is received, the room
warm-up
should be heated up as fast as possible (if
necessary). The thermostat will only allow
heating
Cool
Thermostat is only allowed to provide cooling
Night purge
Not supported by fan coil applications
Pre-cool
If "Pre-cool" is received, the room should be
cooled down as fast as possible (if
necessary). The thermostat will only allow
cooling
OFF
Thermostat is not controlling the outputs,
which means all outputs go to off or 0%
Emergency
The thermostat should heat as much as
heat
possible. The thermostat will only allow
heating
Fan only
All control outputs are set to 0% and only the
fan is set to high speed.
Function will be terminated by any operation
on the thermostat
With all other commands, the thermostat behaves like in Auto mode, i.e. heating or
With all other commands
cooling according to demand.
cooling according to demand.
RDF301, RDF301.50..., RDF600KN
RDF301, RDF301.50..., RDF600KN, RDF600KN/S
can be influenced by a building automation and
following commands:
the thermostat behaves like in Auto mode, i.e. heating or
Basic Documentation
ocumentation
Application mode".
Control sequence
enabled
Heating and/or cooling
Heating only
Heating only
Cooling only
N/A (= Auto)
Cooling only
Neither heating nor
cooling
Heating only
Run fan in high speed