3.13.4 Parameters of the "Expert level with
diagnostics and test"
Name
Expert level
P-band/Switching differential for
P30
heating mode
P-band/Switching differential for
P31
cooling mode
P33
Dead zone in Comfort mode
P34
Setpoint differential
P35**
Integral time
Heating/cooling changeover
P36**
switching point for cooling
Heating/cooling changeover
P37**
switching point for heating
P38****
Input X1
Operating action for X1 if digital
input
P39****
P40****
Input X2
Operating action for X2 if digital
P41****
input
P44***
Actuator running time Y11/Y21
P46
Y2x load current
On time minimum for 2-pos output
P48
control
Off time minimum for 2-pos output
P49
control
P50
Purge time
P51
Flow temp limit floor heating
P52
Fan control
P53
Fan speeds
P54*
Fan overrun time
P55
Fan speed switching point high
P56
Fan speed switching point med
P57
Fan speed switching point low
P58
Fan start kick
P59
Fan minimum on time
P60
Periodic fan kick Comfort
P61
Periodic fan kick Eco
RDF302 Basic documentation
Factory
Range
setting
2 K
0.5 ... 6 K
1 K
0.5 ... 6 K
2 K
0.5 ... 5 K
2 K
0.5 ... 5 K
5 min
0...10 min
16 ° C
10...25 °C
28 ° C
27...40 °C
0 = --- (no function)
1 = Room temp ext. sensor /
Return air temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)
8 = Monitor input (Temp)
3 = Op mode c/o
NO = Normally Open
NC = Normally Close
NO
0 = --- (no function)
1 = Room temp ext. sensor /
Return temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)
1 = Ext. sensor
8 = Monitor input (Temp)
0 = Normally Open
0 (N.O.)
1 = Normally Close
150 s
20...300 sec
0.0 A
0.0 to 5.0 A
1 min.
1...20 min
1 min.
1...20 min
OFF:
1...5 min: Active with selected
OFF
OFF
OFF, 10...50 ° C
0 = Disabled
1 = Enabled
2 = Heating only
1
3 = Cooling only
1 = 1-speed
2
2 = 3-speed
60 sec
0...360 sec
100%
80...100%
65%
30..75%
10%
1...15%
ON: Enabled
ON
OFF: Disabled
2 min
1...6 min
0
0...89 min, OFF(90)
OFF
0...359 min, OFF(360)
Not active
duration
49 / 62
CE1P3079en
2022-06-17