Zone Addressing In Lte Mode (In Conjunction With Synco) - Siemens RDU341 Basic Documentation

Semi-flush mount room thermostats with knx communications
Hide thumbs Also See for RDU341:
Table of Contents

Advertisement

Geogr. zone 2.5.1 or 2.1.1
Outside temperature zone 1
Engineering and
commissioning
Siemens
Building Technologies
Time Switch
Operating mode
Sensor
Outside temperature
Outside temperature
· For a detailed description of KNX (topology, bus supply, function and setting of
LTE zones, filter tables, etc.), see "Communication via the KNX bus for Synco
700, 900 and RXB/RXL, Basic Documentation" [6]
· LTE mode data points and settings are described in the Synco Application
Manual [12]
· To engineer and commission a specific system, use the Synco700 planning and
commissioning protocol (XLS table in HIT, [7])
3.10.3 Zone addressing in LTE mode (in conjunction with
Synco)
In cases where RDU KNX room thermostats are used in LTE mode (e.g. in
conjunction with Synco), zone addresses need to be allocated.
The following zone address must be defined together with the Synco devices at the
planning stage depending on the application.
Short description
Geographical zone (apartment)
Geographical zone (room)
Air distribution zone
Note: "Subzone" of "Geographical zone" is fix 1 (not adjustable)
The device will send and receive LTE communication signals only if the zone
address is valid (not OSV = out of service).
RDU341 Basic Documentation
RDU
Geogr. zone 2.5.1
Room temperature
Operating mode
Air distr zone 1
Air demand
Outside temperature zone 1
Factory setting
--- (out of service)
1
--- (out of service)
Air handling unit
Air distr zone 1
Air demand
Parameter
P82
P83
P87
37 / 68
CE1P3172en
2015-06-08