6.3.3 Sealing end at a building's structure

If HVI
power Conductor are installed on a building's structure, the calculated separation distance
®
"s" in the sealing end range must be maintained from the metal parts in the building´s structure.
The sealing end range ranges from the EB connection element to the connection of the earth connec-
tion element (see Fig. 13).
The mechanical contact with the EB element (semiconductive sheath) allows to discharge lightning
impulse voltages to a reference potential. To this end, a conductive connection to the next equipotential
bonding system (equipotential bonding level) of the installation is required.
A UNI disconnecting clamp (Part No. 459 200, 200 kA) is used to connect the earth connection element
of the HVI
power Conductor to the earth-termination system.
®
Detail A:
EB element
Detail B:
connection of the earth connection
element
s
Figure 13 Sealing end range on a building's structure
EB connection element
Detail A
(Part No. 410 239)
connection to the
building´s equipoten-
tial bonding system
EB
®
HVI
power Conductor
building's structure
earth connection element
Detail B
down conductor
connection to the
earth-termination system
holder, e.g.
Part No. 275 249
s
disconnecting clamp,
Part No. 459 200