6. Installation

6.1
Installing HVI
Before installing the supporting tube, insert and fix the head piece of the pre-assembled HVI
Conductor into the supporting tube and fix it (see also page Figure 5., page 20).
The following steps must be observed:
Unscrew the locking screw of the head piece (M8 x 25 mm) at the head of the supporting tube.
Â
Insert the HVI
power Conductor from below into the supporting tube. To this end, the compressive
®
Â
strength of the integrated EB spring element must be overcome. The conductor can be inserted and
removed several times. To contact the head piece, insert the HVI
porting tube as far as it will go and hold it there.
Firmly tighten the locking screw (M8 x 25 mm) again using a tightening torque of 15 Nm. This en-
Â
sures that the head piece is fixed in the supporting tube and that is electrically connected (capable
of carrying lightning currents). Make sure that there is a sufficient distance (about 7 mm) between
the screw head and the supporting tube after tightening the locking screw. The adhesive coating
of the screw only hardens after about 5 minutes so that the screw can be correctly positioned and
tightened during this period. After hardening of the adhesive coating, the screw must be replaced by
a new one when the screw is removed.
Check whether the HVI
Â
Proper installation can be verified by slightly pulling the conductor at the point where it leaves the
supporting tube.
The relevant air-termination tip or rod must be installed before or after the supporting tube has been
Â
installed depending on the configuration of the installation.
Insert the air-termination tip or rod from above into the head of the supporting tube and tighten the
Â
two locking screws (M8 x 16 mm / M8 x 10 mm) using a tightening torque of 15 Nm.
power Conductors in the supporting tube
®
power Conductor is properly fixed in the supporting tube (see Fig. 5).
®
power Conductor into the sup-
®
power
®
19