Multi-function Output Terminal Delay Time Settings
Set on-delay and off-delay times separately to control the output terminal and relay
operation times. The delay time set at codes OU.50–51 applies to multi-function output
terminal (Q1) and relay (Relay), except when the multi-function output function is in fault trip
mode.
Group Code
Multi-function output
50
On delay
Multi-function output
OU
51
Off delay
Select multi-function
52
output terminal
* Displayed as
Output Terminal Delay Time Setting Details
Code
Select terminal type for relay and multi-function output terminal. An
additional three terminal type selection bits at the terminal block will be
added when an expansion I/O is added. By setting the relevant bit to 0, it
will operate A terminal (Normally Open), and setting it to 1 will operate B
terminal (Normally Closed). Shown below in the table are Relay 1 and Q1
settings starting from the right bit.
OU.52 DO NC/NO
Sel
Name
LCD Display
DO On Delay 0.00
DO Off Delay 0.00
DO NC/NO
Sel
on keypad.
Item
Keypad
LCD keypad
Learning Advanced Features
Parameter
Setting
00*
Description
bit on
Setting
Unit
Range
0.00–100.00 s
0.00–100.00 s
00–11
bit
bit off
245
Need help?