Occupancy Sensor Setup; Associating Wireless Occupancy Sensors - Lutron Electronics GRAFIK Eye QS Quick Installation And Operation Manual

With dali control unit
Table of Contents

Advertisement

Occupancy Sensor Setup

Associating Wireless Occupancy Sensors and GRAFIK Eye QS Wireless
Control Units (for wireless-enabled units only)
1. Make sure the wireless mode of the GRAFIK Eye QS
Main Menu
control unit is "Enabled".
Zone Setup
2. Enter programming mode.
3. Use the Master buttons to highlight "Sensor setup" and
Sensor Setup
press the OK button to accept.
4. Use the Master buttons to highlight "Add wireless
Sensor Setup
sensors" and press the OK button to accept.
Add Wireless Sensors
5. Press and hold the "Lights Off" button (
occupancy sensor for 6 seconds. The lens will start flashing and the
Daylight
info screen on the GRAFIK Eye QS Wireless control unit will display
the sensor's serial number.
Add Wireless Sensors
6. Press the OK button on the GRAFIK Eye QS control unit.
A screen will confirm that the sensor has been assigned.
Initiate Association
To disassociate a wireless occupancy sensor from the GRAFIK Eye
of Sensors
QS control unit, refer to the Radio Powr Savr occupancy sensor
install guide to return the sensor to its "out-of-box" functionality.
Doing so will remove its programming from the GRAFIK Eye QS
Occupancy
control unit.
××××-××××
7. Repeat the above steps for all desired sensors.
8. Exit programming mode.
Press OK to Save
Associating Wireless Occupancy Sensors through QS Sensor
Modules (QSM)
1. Press and hold the Program button on the QSM for 3 seconds to
*Assigned*
enter programming mode. There will be 1 audible beep and the
Status LED will begin flashing. The info screen on the GRAFIK Eye
QS control unit will display that the QSM is in programming mode.
2. Press and hold the "Lights Off" button (
occupancy sensor for 6 seconds. There will be 3 audible beeps
from the QSM to verify association.
3. Press and hold the Program button on the QSM for 3 seconds to
exit programming mode.
Note: The wireless signal has a range of 9 m through standard
construction or 18 m line-of-sight.
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye QS with DALI
16
g
on some sensors) on the
g
on some sensors) on the
Control Unit Quick Installation and Operation Guide
®
9-16
1-8
OK
Radio Powr Savr
Occupancy Sensors
QS Sensor Module (QSM)
(continued on next page...)
Master buttons
OK button
Timeclock (back)
button
Press and hold
g
"Lights Off" or
button to associate/
disassociate
Program button
16

Advertisement

Table of Contents
loading

Table of Contents