Hardware Installation - GE IC695CNM001 Quick Start Manual

Pacsystems rx3i series canopen master module intelligent platforms programmable control products
Table of Contents

Advertisement

2. Hardware Installation

A CNM001 module must be installed in the main RX3i rack in any
slot except slot 0 or the expansion slot. A CNM001 module in an
RX3i Universal Backplane can be installed or removed while power
is applied to the system (hot swapped).
This product is intended for use with the RX3i system. Its
components are considered open equipment [having live electrical
parts that may be accessible to users] and must be installed in an
ultimate enclosure that is manufactured to provide safety. As a
minimum, the enclosure shall provide a degree of protection
against solid objects up to 12mm (e.g. fingers). This equates to a
NEMA/UL Type 1 enclosure or an IP20 rating (IEC60529) providing
at least a pollution degree 2 environment. For use in hazardous
areas, see 2.1, "Installation in Hazardous Areas."
Inserting or removing a module with power applied to the
system may cause an electrical arc. This can result in
unexpected and potentially dangerous action by field
devices. Arcing is an explosion risk in hazardous locations.
Be sure that the area is non-hazardous or remove system
power before removing or inserting a module.
For details about installing RX3i rack systems, refer to GFK-2314.
6
PACSystems* RX3i CANopen Master Module Quick Start GFK-2837
Warning

Advertisement

Table of Contents
loading

Table of Contents